400 Amp Automatic Transfer Switch (HTS-N) Buy with set and save $121.00 off our normal price! Include In Order (+$2,299.00)
Qty: 1 included Usually ships in 3 to 5 days
600 Amp Automatic Transfer Switch (HTS-N) Buy with set and save $229.00 off our normal price! Include In Order (+$4,340.00)
Qty: 1 included Usually ships in 3 to 5 days
800 Amp Automatic Transfer Switch (HTS-N) Buy with set and save $232.00 off our normal price! Include In Order (+$4,407.00)
Qty: 1 included Usually ships in 3 to 5 days
Voltage/Enclosure:
Usually ships in 3 to 5 days
Questions? Call us anytime at (800) 608-3270.
Quantity:
The very successful and well known line of Guardian automatic standby generators is manufactured by Generac Power Systems. Generac Power Systems specializes in manufacturing fully integrated power systems that include industrial, commercial, and residential...
More on Guardian...
80 kW Guardian Elite Commercial Series Liquid Cooled Automatic Standby Generator
This generator is ideal for a broad range of enterprises, including restaurants, convenience stores, supermarkets, banks, fitness centers, hotels, and retail outlets. Keep your business "in business" and protect your revenue stream by investing in a reliable yet affordable back-up power source. One of the quietest liquid cooled generators on the market this model features the exclusive patent-pending Whisper-Test low speed generator test cycle which reduces noise by 50%. Achieves near silent operation that satisfies all known sound ordinances.
Features:
Liquid cooled engine produces more electricity for longer outages
Whisper-Test™: Patent-pending, self-test feature makes the GUARDIAN Elite 50% quieter during the generator’s weekly self-test cycle
Aluminum Enclosure: Corrosion resistance for coastal communities
Longest life expectancy in the industry: Over 3,000 hours of run time
Superior Paint: Tough, textured powder coat finish for unmatched durability and all weather protection
UL listed
Clean burning fuel: Natural gas or liquid propane vapor
400 Amp Automatic Transfer Switch (HTS-N)
This product makes the difference between a truly automatic generator set and just another generator. When the power goes out, this switch automatically senses the failure, turns on your generator, and routes electricity to the circuits of your home. No toggles to flip, no knobs to turn, no extension cords to run during a blackout. You will have the comfort and peace-of-mind knowing that your Guardian stand-by generator does everything for you...automatically!
Features:
Single coil design, electrically operated and mechanically held
Programmable exercise time
SPDT aux contacts
Main contacts are silver alloy
Conformal coating protects the printed circuit board
UL 1008 listed
Indicating LED's for switch position, standby operating, and utility available
3 positions test switch: Fast test, auto, normal test
Arc chutes on main contacts
Signal before transfer contacts
Rated to all classes of loads
Remote start, stop and transfer through GenLink Communications Software
Specifications:
Designed to operate in conjunction with the Generac H100 Series generator controller
2-wire RS485 communication link to the generator controller
Switch operation is instigated by the generator controller
All timers and voltage set points are programmable through GenLink Communications Software
600 Amp Automatic Transfer Switch (HTS-N)
This product makes the difference between a truly automatic generator set and just another generator. When the power goes out, this switch automatically senses the failure, turns on your generator, and routes electricity to the circuits of your home. No toggles to flip, no knobs to turn, no extension cords to run during a blackout. You will have the comfort and peace-of-mind knowing that your Guardian stand-by generator does everything for you...automatically!
Features:
Single coil design, electrically operated and mechanically held
Programmable exercise time
SPDT aux contacts
Main contacts are silver alloy
Conformal coating protects the printed circuit board
UL 1008 listed
Indicating LED's for switch position, standby operating, and utility available
3 positions test switch: Fast test, auto, normal test
Arc chutes on main contacts
Signal before transfer contacts
Rated to all classes of loads
Remote start, stop and transfer through GenLink Communications Software
Specifications:
Designed to operate in conjunction with the Generac H100 Series generator controller
2-wire RS485 communication link to the generator controller
Switch operation is instigated by the generator controller
All timers and voltage set points are programmable through GenLink Communications Software
Standby Accept Voltage: 85-95%
Standby Accept Frequency: 85-95%
Nominal Voltage: 1 Volt Increments
Allowable Deviation of Utility: 1 - 100%
Line Interruption Delay: 1 - 10 seconds
Engine Warmup Time: 1 - 300 seconds
Minimum Run Time: 5 - 60 min.
Return to Utility Timer: 1 - 30 min.
Engine Cooldown Timer: 1 - 30 min.
Signal Before Transfer Timer: 1 - 30 sec.
Transfer Type: Inphase Time Delay Neutral
Terminal Lug Wire Contact Terminals: Two Lugs per pole - 500MCM - 1 AWG
800 Amp Automatic Transfer Switch (HTS-N)
This product makes the difference between a truly automatic generator set and just another generator. When the power goes out, this switch automatically senses the failure, turns on your generator, and routes electricity to the circuits of your home. No toggles to flip, no knobs to turn, no extension cords to run during a blackout. You will have the comfort and peace-of-mind knowing that your Guardian stand-by generator does everything for you...automatically!
Features:
Single coil design, electrically operated and mechanically held
Programmable exercise time
SPDT aux contacts
Main contacts are silver alloy
Conformal coating protects the printed circuit board
UL 1008 listed
Indicating LED's for switch position, standby operating, and utility available
3 positions test switch: Fast test, auto, normal test
Arc chutes on main contacts
Signal before transfer contacts
Rated to all classes of loads
Remote start, stop and transfer through GenLink Communications Software
Specifications:
Designed to operate in conjunction with the Generac H100 Series generator controller
2-wire RS485 communication link to the generator controller
Switch operation is instigated by the generator controller
All timers and voltage set points are programmable through GenLink Communications Software
Standby Accept Voltage: 85-95%
Standby Accept Frequency: 85-95%
Nominal Voltage: 1 Volt Increments
Allowable Deviation of Utility: 1 - 100%
Line Interruption Delay: 1 - 10 seconds
Engine Warmup Time: 1 - 300 seconds
Minimum Run Time: 5 - 60 min.
Return to Utility Timer: 1 - 30 min.
Engine Cooldown Timer: 1 - 30 min.
Signal Before Transfer Timer: 1 - 30 sec.
Transfer Type: Inphase Time Delay Neutral
Terminal Lug Wire Contact Terminals: 4 Lugs per pole - 500MCM - 4/0 AWG